FORNEY Fire Detection Renovation Case
Background of the project
◆ Boiler information: 2X330 MW square tangential boiler
◆ Manufacturer: Shanghai Boiler Works Co., Ltd.
◆ Number of coal burners: 24
◆ Number of oil burners: 12
There is a problem
◆ The original equipment is seriously aging, the fire detection is unstable, and the anti-interference ability is poor;
◆ The original fire detection probe has low temperature resistance, frequent fault alarms, and a high failure rate;
◆ The product has poor adjustability and cannot adapt to complex combustion conditions;
Solution
◆ Replace the original Foreny IDD fire detection probe with Safe-Fire’s EZ-FLAME series fire detection probe, which has stable performance and strong anti-interference ability;
◆ The new fire detection probe has a temperature resistance of 85°C and can adapt to high temperatures and high dust. Working conditions;
◆ EZ-FLAME fire detector can accurately detect the burning condition of the target flame in real time by adjusting parameters such as bandwidth, frequency, gain, etc.;
◆ Safe-Fire's EZ-FLAME series of fire detectors have a short delivery cycle and high cost performance.
On-site installation photos
Transformation of the former
After transformation
Specifications
product name |
IDD |
EZ-FLAME |
brand name |
FORNEY |
SAFE-FIRE |
Spectral response range |
400-3300nm |
900-1700nm |
signal processing technology |
Ordinary processor |
DSP high speed microprocessor |
Operating environment temperature |
0℃-+60℃ |
-40℃-+85℃ |
Protection level |
IP66 |
IP66 |
Debugging mode |
Handheld Communicator |
Panel debugging, network debugging |
Detection performance |
Detect AC (flicker amplitude) and frequency signals, no bandwidth settings, frequent debugging is required after coal quality changes |
AC (flicker amplitude) and frequency signals, with bandwidth settings to prevent mixed detection of kerosene, prevent low-load peeking, strong adaptability |
output signal |
"Fire" switch value, fault alarm, flame intensity: 4-20mA |
"Fire" switch value, fault alarm, flame intensity: 4-20mA |
Result
◆ The fire detection signal detection is stable, which improves the safety of the fire detection system;
◆ The fire detection protection is put into normal operation, improving the safety of the boiler;
◆ The fire detection probe does not need to be debugged, reducing the maintenance workload and improving the user experience.