SFT-EZS1 Flame Detector Tester Catalog

SFT-EZS1 flame detector tester is suitable for the diagnosis of some functions of the EZS-IR and EZS-UV flame scanner.


The tester provides a light source signal that simulates the emission of infrared or ultraviolet light from a flame as a signal input to the flame scanner. 


The panel of the tester is equipped with two ammeters and one voltmeter, which are used to detect the current value of the±12V power supply input from the flame scanner and the voltage value of the flame signal strength output by the flame scanner. The tester is integrated into an industrial-grade carrying case, which is easy to carry and also contributes to the protection of the tester.

SFT-EZS1 Flame Detector Tester Catalog
Download

Product Features

• Portable Design, Convenient to Use
• Simple Interface, Easy to Operate
• Rapid Diagnosis With Immediate Results

Specifications

P/N

Input Power

Operating Temp.

Suitable For

Weight

60-380-0008

100-240Vac, 50/60Hz

0℃  to +70℃

EZS-IR、EZS-UV

4.35 kg

 

 

Operating Function


NO.

Component

Function

1

IR Indicator

IR LED emit light when this indicator is on

2

Toggle Switch

IR and UV light source control switch, upward toggle, IR indicator on, emit IR LED light, downward toggle, UV indicator on, emit UV LED light, put in the middle, IR and UV indicators off, IR and UV LED are not emitting light

3

UV Indicator

UV LED emit light when this indicator is on

4

Placement Slot

Placement of the flame scanner to be tested

5

IR and UV LEDs

Emits infrared and ultraviolet LED light

6

Communication Cable

Connect the flame scanner to tester

7

Power Cord

Power cable of the tester

8

-12V Ammeter

Indicates the current value of the flame scanner under test when a -12V power supply is input.

9

-12V Indicator

Indicates that the voltage of the -12V power supply output by the tester is normal.

10

+12V Ammeter

Indicates the current value of the flame scanner under test when a +12V power supply is input.

11

+12V Indicator

Indicates that the voltage of the +12V power supply output by the tester is normal.

12

Power Switch

The tester power switch with indicator light to control the tester power on or off.

13

Flame Signal Strength Voltmeter

The tester power switch with indicator light to control the tester power on or off.

14

FLAME ON Indicator

Indicates that the flame signal strength voltage output from the flame scanner under test is greater than the “flame on" threshold set by the tester. Indicates that the flame scanner under test is capable of observing the flame.

15

FLAME OFF Indicator

Indicates that the flame signal strength voltage output from the flame scanner under test is less than the “flame off" threshold set by the tester. Indicates that the flame scanner under test cannot observe a flame.

16

Power Socket

Tester input power socket, permitted power 220Vac, 50Hz

Picture Name